New standards, old homes – a brief review

One usually does not need to upgrade existing work to current standards if the existing work is legal and safe. Legal work means it complied with standards and manufacturer’s instructions, if any, when the work was done. New work and additions to, extensions of, replacements of and major repairs to existing work should comply with standards and manufacturer’s instructions in effect when the work was performed.

bathroom remodelling

Bathroom remodeling electrical issues

Adding a sink is a common part of a bathroom remodel. Each sink basin should be served by a receptacle, so a GFCI protected receptacle should be added when a sink is added unless the existing receptacle(s) will properly serve both sinks. The receptacle should be within 36 inches from the basin’s edge. The receptacle may be located on the wall or on the cabinet; but it shouldn’t be more than 12 inches below the counter top. These locations are so people don’t have to run extension cords to serve their bathroom appliances.

A common practice in older homes was to have a receptacle in a light fixture. That might work in a remodel if the receptacle is grounded and on a GFCI-protected circuit; however, required receptacles may not be more than 66 inches above the floor. A light fixture at that height would be a safety hazard, so receptacles in light fixtures are impractical at best.

Remember to check that the receptacles do not move, especially those mounted in mirrors. Receptacles that move may cause loose connections that may arc and cause a fire.

Speaking of receptacles (and switches, too), it should go without saying that they shouldn’t be located on the walls or ceilings above a tub or shower; but occasionally people don’t get the memo. It doesn’t matter how high the receptacle or switch is mounted or whether they are GFCI-protected, they shouldn’t be above a tub or a shower.

People love to install ceiling (paddle) fans and chandeliers in bathrooms. That’s fine so long as they aren’t too close to a tub or a shower. No part of a hanging light fixture or a ceiling fan may be within 3 feet horizontally and 8 feet vertically from the tub deck or shower pan. No part includes nonconductive parts such as wood fan blades, as well as potentially conductive parts such as pull chains.

Light fixtures less than 8 feet directly above a tub or a shower should at least be listed for use in damp areas and should be listed for wet areas if they are subject to contact with liquid water. It’s hard to tell how a light fixture is listed without some dismantling. Use good judgment before making a big deal about this issue.

People rarely use them, but whirlpool tubs sure look good and people add them to bathrooms. The pump motor should be served by a dedicated GFCI-protected circuit, often 20 amps. If a receptacle that is only accessible from the service access serves the motor, the receptacle should face the opening and should be located within 12 inches of the opening. This is a new requirement, so many older homes won’t comply.

A whirlpool tub motor with a bonding lug should be bonded to metal water supply pipes using at least #8 copper wire. This is in addition to any equipment grounding wire connected inside the motor. That said, there is usually little practical safety benefit from this bonding connection because most whirlpool tub pumps have no metal in contact with the water. Use good judgment before making a big deal about this issue.

And while we’re on the subject of whirlpool tubs, let’s make sure someone really can get to the tub motor for service and replacement. The opening should provide useful access to the tub motor, so it shouldn’t be obstructed by framing or by other obstructions that limit motor access. The access opening should be at least 12 by 12 inches and, if the motor is more than two feet from the opening, the opening should be at least 18 by 18 inches.

Bathroom remodeling plumbing issues

Where to begin? There are so many issues to choose from.

Let’s start with flexible tailpieces, which also get installed as trap arms and even traps. This flexible material is not allowed. All drainage pipes and fittings should be smooth-wall material with no ridges, ledges or bends that will slow down or stop flow. This flexible stuff is unsanitary and has a greater tendency to clog. Here’s another case of just because you can buy it at your local big-box store doesn’t mean you should.

It’s OK to drain a new sink into the existing trap, but there are limits. The distance between a plumbing fixture outlet and the trap should not be more than 30 inches horizontally.

What about adding a bathroom in a basement? You should see a backwater valve if any fixture flood rim and the building drain are below the nearest upstream sewer manhole cover. A backwater valve is a one-way valve that lets the fixtures discharge into the building drain, but prevents back flow from a clogged sewer from entering the home. The backwater valve should be accessible and have a watertight cover. Look for backwater valves. It’s easy to overlook something that’s not there.

An ejector will be necessary if the building drain is above the basement fixtures. Only those fixtures below the building drain should drain into the ejector. A full-open valve and a check valve should be installed near the ejector on the discharge side. The ejector should have a gas and watertight seal and should be accessible. The ejector should be vented either to an external vent or, where permitted, by an air admittance valve.

If you can see where the ejector drain pipe connects with the building drain or a branch drain, make sure the connection is made with a drainage fitting such as a wye, tee-wye or a long-turn 90° elbow. All fittings should enter the drain pipe above the drain pipe’s center line.

Here are a couple of practical issues surrounding ejector pumps. A high-water alarm with a battery backup, while not required, is a good idea for all ejector and sump pumps. These inexpensive devices sound an alarm when the water level in the pit reaches a certain predetermined level to help avoid gross stuff spilling all over the place. Ejector pumps won’t work when the power is out, so you might want to not use the fixtures that drain into the ejector until power returns.

Bathroom space issues

Sometimes, people try to squeeze bathrooms into smaller spaces than they should. This can lead to some pretty tight clearances between bathroom fixtures and obstructions. Tight clearances are both a convenience issue and a safety hazard. We don’t want people bumping their heads or tripping and falling in wet bathrooms. The elderly and people with impaired mobility are most at risk when there is inadequate clearance at bathroom fixtures.

The general rule is that bathroom ceiling height should be at least 84 inches in most parts of the room. Toilets (including bidets in really fancy houses) and sinks should have headroom clearance of at least 80 inches at a point 10 ½ inches in front of the fixture.

Toilets should have at least 15 inches clearance to side obstructions such as walls, tubs and showers. Measurement is from the center of the toilet. Toilets and sinks should have at least 21 inches (more in some jurisdictions) clearance in front.

Showers and tubs are dangerous slip-and-fall hazard areas, so the minimum clearances are especially important. Showers and tubs with a shower head should have headroom clearance of at least 80 inches for a 30-by-30-inch area under the shower head. Shower floors should have a minimum area of 900 square inches, with a minimum dimension of 30 inches. A 25-inch minimum dimension is OK if the shower area is at least 1,300 square inches.

Showers should have at least 24 inches clearance in front of the opening and an opening that is at least 22 inches wide. Shower doors, if any, should slide or swing out. They may swing in, too, if they also swing out.

The bottom line

Homeowners and house flippers love to remodel bathrooms. Why not? Next to kitchen remodeling, bathrooms are one of the best bangs for the remodeling buck. Bathroom remodeling deficiencies, whether done through ignorance or carelessness, are quite common. Take your time in remodeling the bathroom so it meets all safety and building code requirements.